Cette configuration a les caractéristiques suivantes:
Electrical Power TestHipot TestingCliquez sur 'Configurez votre produit' et nous vous contacterons pour vous adresser un devis conforme à votre besoin.
Vous pouvez cliquer sur Contactez-moi, si vous préférez, et nos experts vous guideront vers la bonne solution technique et financière.
VLF Sine Wave 62 kV Test and diagnostics system for medium voltage cables.
Portable 62 kV VLF test and diagnostic system for medium-voltage cables, with standard sheath testing and optional Tan Delta and partial discharge diagnostics.
Simplify medium-voltage cable testing and diagnostics with the VLF Sine Wave 62 kV, a compact, portable, high-performance system designed for commissioning tests, condition assessment, and sheath testing. The unit delivers a true VLF sine-wave output up to 44 kVrms/62 kVpeak, supports DC testing up to ±62 kV, and automatically adjusts frequency to match cable length and load, helping you test both short and long cable sections reliably.
The system combines multiple functions in one platform. In addition to monitored withstand testing, it also performs sheath testing and sheath-fault pinpointing up to -20 kV when used with the ESG NT2 step-voltage probe. With the optional internal Tan Delta function, it also supports cable condition assessment with automatic result interpretation in line with IEEE 400.2, giving users a clearer view of cable ageing and insulation behaviour.
User experience is built into the design. The large 7-inch colour touchscreen and touch-friendly software make setup and operation straightforward, even for more advanced diagnostic routines. The analogue residual voltage indicator keeps the operator informed about cable status, while automatic discharge, breakdown detection and optional external safety equipment help support safe testing practice in the field.
All measurements are stored in the unit’s internal memory and can be reviewed directly on the instrument or exported via USB for reporting in MeggerBook Lite, which is included. The system is also prepared for wireless data transfer. For users who need partial discharge diagnostics, the VLF Sine Wave 62 kV can be paired with the optional PDS 62-SIN PD coupler to create a more complete test and diagnostic solution covering monitored withstand testing, Tan Delta diagnosis and PD diagnosis.
For applications that demand portability without compromising performance, the VLF Sine Wave 62 kV offers a strong balance of output capability, usability and integrated diagnostics.
| KEY FEATURES |
| Performs cable withstand testing, cable diagnostics and sheath fault pinpointing |
| Smallest and lightest unit on the market in its clas |
| Unique user-experience thanks to large colour-touch display |
| Automatic result interpretation as per latest IEEE 400.2 standard |
| Highest safety thanks to analogue residual voltage indicator |
| BENEFITS | |
| Portable High-Performance Testing | The VLF Sine Wave 62 kV combines a high output voltage with a compact portable design, giving users a powerful field-ready solution for medium voltage cable testing without the complexity of a larger setup. |
| One System for Multiple Test Tasks | Carry out VLF withstand testing, DC testing, sheath testing and sheath fault pinpointing with one platform. Add the optional internal Tan Delta function for cable condition assessment and expand further with the PDS 62-SIN for partial discharge diagnostics. |
| Fast, Intuitive Operation | The large colour touchscreen, touch-friendly interface and straightforward workflows reduce training time and make even advanced diagnostic procedures easier to perform with confidence. |
| Built-in Data Handling and Reporting | Measurements are automatically evaluated and stored in internal memory, can be reviewed on the unit, and exported through USB for fast report generation in MeggerBook Lite. |
| Safety-Focused Design | Automatic discharge, breakdown detection and the analogue residual voltage indicator help users stay informed about cable status during testing, while optional external safety equipment supports safer field operation. |
| SPECIFICATIONS | |
| Model: VLF SINE 62 kV Test and Diagnostics System for Medium Voltage Cables | |
| Feature | Parameter |
| OUTPUT VOLTAGE | |
| VLF Sine Wave | 0 … 44 kVRMS / 0 ... 62 kVpeak |
| DC Voltage | ± 0 … 62 kV |
| VLF Rectangular Voltage | 0 … 62 kV |
| Accuracy | ± 1 % |
| Resolution | 0.1 kV |
| OUTPUT CURRENT | |
| Source Output Current | 23 mA @ 62 kVpeak |
| Accuracy | ± 1 % |
| Resolution | μA |
| Frequency Range | 0.01 ... 0.1 Hz autom. frequency adjustment |
| Output Load | 1 μF @ 0,1 Hz at 44 kVRMS 10 μF maximum test capacity |
| INTERNAL TAN DELTA | |
| Measuring Frequency | 0.01 ... 0.1 Hz |
| Measuring Range | 10-4...100 |
| Accuracy | 10-4 |
| Resolution | 10-5 or 10-6 |
| Sheath Testing | 0 … -20 kV DC |
| Sheath Fault Pinpointing | 0 … -20 kV DC Pulse rate 0.5:1, 1:2, 1:3 and 1:4 |
| GENERAL | |
| Safety | autom. discharging of the test object and residual voltage indicator |
| Input Voltage | 100 V … 264 V, 50/60 Hz, 2000 VA |
| Duty Cycle | continuous |
| Display | 7” colour-touchscreen |
| Interfaces | USB, LAN, wireless (coming soon) |
| Internal Memory | For at least 1000 measurements |
Dimensions (W x H x D) | 530 (670*) x 640 x 510 mm 20.9 (26.4*) x 25.2 x 20.1 in. |
| Weight | 59 kg 130 lbs. |
| Protection Class | IP 21 |
| Operating Temperature | - 20 °C … + 55 °C -4 °F … 131 °F |
| Storage Temperature | - 20 °C … + 70 °C -4 °F … 158 °F |
NOTE:
* Including Carrying Handles
| SPECIFICATIONS | |
| Model: VLF SINE 62 kV Test and Diagnostics System for Medium Voltage Cables | |
| Product / Order Number | Description |
| VLF SINE 62 kV / 1015090 | VLF SINE 62 kV with 5 m HV Lead |
| VLF SINE 62 kV / 1015091 | VLF SINE 62 kV with 10 m HV Lead |
| VLF SINE 62 kV / 1016941 | VLF SINE 62 kV with 15 m HV Lead |
| MANDATORY SELECTION MAINS CABLE (1x) | |
| 810000024 | Mains cable EU |
| 118307335 | Mains cable UK |
| 502025220 | Mains cable US |
| 90020435 | Mains cable AUS |
| MANDATORY SELECTION CLAMP SET (1x) | |
| 2016176 | Clamp set EU VLF SINE 62 kV |
| 2016300 | Clamp set US VLF SINE 62 kV |
| OPTIONS | |
| 138316309 | Internal tan delta |
| 1013605 | HVCC VLF SIN-62, leakage current correction |
| 2010001 | External safety unit without controls |
| 2006112 | External safety unit with controls |
| 1013586 | Test adapter VLF CS-SF6-UNI-L set (long 460 mm) |
| 1013587 | Test adapter VLF CS-SF6-UNI-K set (short 310 mm) |
further information on PDS 62-SIN datasheet (Please see Resources) | PDS 62-SIN PD coupler |
| 90041725 | Transport case VLF SINE 62 kV |
| 90023948 | Transport case PDS 62-SIN |
| 1014430 | ESG NT2 step voltage probe |
| 2011622 | Test/calibration certificate VLF SINE 62 kV |
| 2015875 | Software MeggerBook 3 for Windows - full license |