MS 156 amplifier units can be used in combination with any CMC test set or in conjunction with digital real time power system network simulators. The outputs are galvanically separated from the inputs as well as from ground and are used independently or in addition to those of the CMC test sets. The connection to a CMC test set is made by a control cable at the back of the units.
Used for tests requiring
• six independent voltage phases (e.g. for testing synchronizing devices with two independent three-phase voltage systems)
• more current channels than provided by the CMC test sets
Specifications | ||
Omicron VEHV1030 | ||
Technical Data1 | ||
Voltage amplifiers | ||
Features | Parameter | |
Setting Range | 3-phase ac (L-N) | 3 x 0 ... 250 A |
1-phase ac (L-N) | 1 x 0 ... 500 A | |
dc (L-N) | 3 x 0 ... ±250 V | |
Power | 3-phase ac (L-N) | 3 x 75 VA at 75 ... 250 V |
1-phase ac (3L-N) | 1 x 150 VA at 75 ... 250 V | |
1-phase ac (L-N) | 1 x 150 VA at 150 ... 500 V | |
dc (L-N) | 1 x 212 W at ±(150 ... 250 V) | |
Accuracy | error < 0.03 % typ. (< 0.1 % guar.) | |
Distortion (THD+N)2 | < 0.03 % typ., < 0.1 % guar. | |
Bandwidth (-3dB | > 6 kHz | |
Phase lag at 50/60 Hz | 1.95°/2.34° | |
Input voltage | 0 ... 5 V | |
Amplification | 50 V / V | |
Current amplifiers | ||
Setting Range | 3-phase ac (L-N) | 3 x 0 ... 25 A |
1-phase ac (L-N) | 1 x 0 ... 75 A | |
dc (L-N) | 1 x 0 ... ±25 A | |
Power | 3-phase ac (L-N) | 3 x 70 VA at 7.5 A |
1-phase ac (3L-N) | 1 x 210 VA at 22.5 A | |
1-phase ac (L-N) | 1 x 140 VA at 7.5 A | |
dc (L-N) | 1 x 140 W at ± 10.5 A | |
Accuracy | error < 0.03 % typ. (< 0.1 % guar.) | |
Distortion (THD+N)2 | < 0.03 % typ., < 0.1 % guar. | |
Bandwidth (-3dB | > 6 kHz | |
Phase lag at 50/60 Hz | 1.95°/2.34° | |
Input voltage | 0 ... 5 V | |
Amplification | 5 A / V | |
Max. compliance voltage (L-N)/(L-L) | 15 Vpk / 60 Vpk | |
Amplifiers, general3 | ||
Input impedance | > 40 kΩ | |
Galvanic isolation Input/Output | 1.5 kVdc | |
Galvanic isolation amplifier groups | 1.5 kVdc | |
Galvanic isolation amplifier groups | 4mm banana sockets/amplifier combination socket | |
Amplifiers, if controlled by a CMC | ||
Frequency | range sine signals | 10 ... 1000 Hz |
range transient signals | dc ... 3.1 kHz accuracy | |
accuracy/-drift | ±0.5 ppm / ±1 | |
resolution | 5 µHz | |
Phase | angle range | - 360° ... +360° |
resolution | 0.001° | |
error at 50/60 Hz | < 0.02° typ. (< 0.1° guar.) | |
Output voltage resolution | 12 mV | |
Output current resolution | 1 mA | |
Power supply | ||
Nominal input voltage | 110 ... 240 Vac, 1-phase | |
Permissible input voltage 9 | 99 ... 264 Vac | |
Nominal frequency | 50/60 Hz | |
Permissible frequency range | 45 ... 65 Hz | |
Power consumption | < 1000 VA | |
Connection | Standard ac socket (IEC 60320) | |
Environmental conditions | ||
Operation temperature | 0 ... +50°C (+32 ... +122°F) | |
Storage temperature | -25 ... +70°C (-13 ... +158°F) | |
Humidity range | Relative humidity 5 ... 95 %, non-condensing | |
Vibration | IEC 60068-2-6 (20 m/s2 at 10 ... 150 Hz) | |
Shock | IEC 60068-2-27 (15 g/11ms half-sine) | |
EMC | Directive 2004/108/EC (CE conform) EN 61326-1, EN61000-6-4, EN61000-3 | |
Emission | FCC Subpart B of Part 15 Class A | |
Immunity | EN 61326-1, EN61000-6-2, EN 61000-4-2/3/4/5/6/11 | |
Safety | Directive 2006/95/EC (CE conform) EN 61010-1, EN 60950-1, UL 61010-1, CAN/CSA-C22.2 No 61010-1-04 | |
Miscellaneous | ||
Weight | 14.7 kg (32.4 lbs) | |
Dimensions (W x H x D, without handle) | 450 x 145 x 390 mm (17.7 x 5.7 x 15.4 in) | |
Certifications | TÜV-GS, UL, CUL |
Article | Description | Order NO. |
CMA 156 | Current Amplifier (6 x 25 A) | VEHV1010 |
CMA 156 | Current Amplifier (3 X250 V, 6 x 25 A) | VEHV1030 |