Los modelos configurados tienen las siguientes opciones:
Electrical & Power QualityPower Analysis / Recorders / LoggersUtilice "Presupuesto Rápido" y nos pondremos en contacto con usted y le cotizaremos para su necesidad exacta.
También puede ponerse en contacto, si lo prefiere, y nuestros expertos podrán orientarlo con la aplicación y la solución de adquisición adecuadas para este producto.
Lo sentimos pero no disponemos actualmente de ninguna información sobre Especificaciones clave para este producto en línea.
Si desea más información, póngase en contacto y un miembro de nuestro equipo le atenderá.
Designed for portability, the lightweight, battery-powered analyzer eliminates the need to carry large, fragile, expensive analyzers into the field, allowing you to make measurements directly at the load in nearly any environment. By measuring directly at the load, you can discover how the equipment operates under real-world conditions, with real-world variables, not just at a test bench or in the lab.
Combined with wide-band frequency response, it makes it easier than ever to make measurements on hard to access systems such as inverter drive systems, DC-AC and AC-DC power conversion systems, and electric motors without removing them from service. Making these measurements in the field simplifies the troubleshooting, and performance measurement processes without sacrificing uptime, giving you more accurate test results, that will enable you to discover whether your loads are operating as effectively and efficiently as they should be.
| Key Features |
| Key measurements: Voltage, current, active power, reactive power, apparent power, power factor, and harmonics with associated values |
| High accuracy and wide bandwidth - 0.1% measurement accuracy and 500 kHz bandwidth |
| Highly portable and easily installed in tight spaces - only 3.78" (9.6 cm) thick |
| Operate continuously for up to 10 hours without an external power supply using the 5000 mAh Li-ion internal battery |
| Measure safely - safety rated for CAT III 1000V, CAT IV 600 V environments |
| Measure three phase power and DC output power at the same time with three channels, with voltage and current inputs on each channel |
| 0.1% accuracy, 500 kHz bandwidth, 200 ks/s sample rate so you can rely on the power conversion system measurements you take no matter what distortion may be present |
| USB and RS485 interface and open communication protocol for easy system integration and software platform flexibility |
| Combine two analyzers to enable simultaneous measurement of multiple circuits for even more troubleshooting capability - configurable to 6 or 8 channels using dual analyzer synchronization |
| View critical data in the field on the main display - Meter, Waveform, Harmonics up to the 100th, Vector and Trend |
| Ensure high common-mode rejection and allow flexible configurations according to measurement requirements using the electrically isolated channels |
| User adjustable measurement rate from 100 ms to 1 s with continuous logging via 32GB of onboard storage |
| Easy in-field set up using the integrated front panel or a remote PC connection (USB or RS485) |
| Online measuring, data download and analysis with included PC software (Fluke Power Analyzer Software) |
| Full remote control of the connected instrument using Fluke Power Analyzer Software and a local USB or long-distance RS485 connection |
| Applications |
| R&D and third party labs |
| Renewable energy/clean tech |
| Manufacturing |
| Specifications | |
Fluke NORMA 6003 Portable Power Analyzer; 3 channel | |
| Model Overview | |
| Features | Parameters |
| Inputs | 3 Voltage + 3 Current |
| Sample Rate | 200 ks/s |
| Measurement Update Rate | 100 ms, 200 ms, 500 ms, 1s |
| Dual Analyzer Synchronization Mode | Able to extend to 6, 7 or 8 channels (using multiple instruments) |
| Data Trend Storage Rate | As per display rate |
| Main Function | Meter, Scope, Harmonic, Phasor, Trend |
Measuring Parameters | RMS, DC Component, AC Component, Rectified Mean, Peak Value, Peak-Peak, Crest Factor, Form Factor, Fundamental Component, Fundamental Content, Harmonic Distortion, Harmonic Content, Harmonic Factor for voltages and currents, Active Power, Reactive Power, Apparent Power, Power Factor, Phase Shift, Efficiency, Impedance, Electric Energy, Charge/Discharge capacity (Ah), Frequency |
| Range | 10, 100, 1000 V |
| Crest Factor | CF ≤2 |
| Maximum Voltage | 10% overload |
| Input Impedance | 2 MΩ/10 pF (typical) |
| Temperature Coefficient | 0.05 (Spec)/k |
| Bandwidth | 1000 V range: 500 kHz 100 V range: 200 kHz 10 V range:100 kHz |
| CMRR | 120 dB at 50/60 Hz |
| Operating Temperature | 14 to 122°F (-10 to 50°C) |
| Storage Temperature | -22 to 140°F (-30 to 60°C) |
Operating Humidity | Non-condensing (<50°F [10°C]) ≤90% RH (at 50 to 86°F [10 to 30°C]) ≤75% RH (at 86 to 104°F [30 to 40°C]) ≤45% RH (at 104 to 122°F [40 to 50°C]) |
| Altitude | Operating: 6561.68' (2000 m) Storage: 39,370.1' (12,000 m) |
| Display | 5.7", TFT LCD, 640 x 480 |
| Battery | BP 291, 10.8 V/5000 mAh, 54Wh IEC 62133, UN38.3 Operating time: 10 Hours (on battery) |
| Communication Interface | USB/RS485 |
| Storage Capacity | 32GB |
| PC Software | Fluke Power Analyzer software |
| Ingress Protection | IP 50 (Terminals mated) according to IEC 60529 |
| Safety | IEC 61010-1: Pollution Degree 2 IEC 61010-2-030: CAT IV 600V, CAT III 1000 V |
| EMC | IEC 61326-1: Industrial IEC 61326-2-2 |
| Dimensions | 11.73 x 8.46 x 3.78" (298 x 215 x 96 mm) |
| Weight | 7.7 lbs (3.5 kg) |