Configured models contain the following attributes:
Electrical Power TestHipot TestingPlease use 'Get Quick Quote' and we’ll contact you and quote for your exact need.
You can also get in touch, if you prefer, and our experts will be able to guide you with the right application and procurement solution for this product.
Please refer to the Resources section for Datasheets or see the Product Overview.
If you would like to know more, please get in touch and one of our team will be happy to help.
The smallest VLF /DC unit on the market now includes an integrated Tan Delta measurement system to perform advanced electrical insulation diagnostics. For example, this can be extremely useful when performing advanced diagnostics on cable systems as it provides valuable information as to the condition of the cable insulation and shield.
The instrument automatically performs a TD test, stepping up the voltage at the user prescribed levels (according to the IEEE) and stores the results. All test parameters including insulation resistance, capacitance, RMS current and voltage, test durations, voltage steps, tan delta, and standard deviation are all measured and displayed by the HVA28 LCD display or stored to an internal memory.
Test results can also be transferred directly to a USB memory stick or wirelessly via Bluetooth to a PC for later analysis and reporting using the supplied industry leading reporting software -TD Control Center. All units are shipped with a calibration certificate, TD Control Center software, corona protection shields, Bluetooth dongle, and an accessories tote.
Key Features |
Integrated TD unit |
TD Resolution ±1x10-4 |
TD Analysis & Reporting using TD Control Center |
Digital RMS metering |
Smallest unit available |
Bluetooth/USB Mem. stick PC Interface |
Color LCD Display |
Weighs only 31 lbs / 14 kg |
Insulation Resistance & Cap. Measurement |
Perform advanced diagnostics on MV Cables according to IEEE400 and 400.2 |
Output Frequency optimization |
Real time oscilloscope display |
Auto & Manual Test Sequences |
Internal Storage of Test Reports |
Unlimited duty cycle |
Flashover voltage detection |
Power supply immunity and independence |
Low maintenance, oil-free design |
RMS Digital Metering of Current and Voltage |
Benefits | |
Output Modes | VLF 20kVrms/28kV Peak output DC ±28kV Sine/Square/ DC outputs Cable Jacket / Sheath testing mode TD measurement mode Vacuum bottle testing mode Fault Conditioning/Trip Load independent output waveform |
Safety | Short circuit detection Emergency Off button Integrated internal discharge of DUT. 12kV power frequency voltage feedback protection |
Specifications | |
HVA28TD VLF/DC Hipot Tester with Integrated Tan Delta | |
Feature | Parameter |
Power Supply / Input Voltage | 110 to 240V AC ±10% (50/60Hz) |
Input Power Requirements | 400VA |
Rated Max Output Voltage | Sinusoidal RMS/Peak: 20kV/28kV Squarewave: 28kV DC: ±28kV |
Rate Max Output Current | Sinusoidal RMS: 20mA DC/Squarewave: 28mA |
Output Frequency (default 0.1Hz) | 0.01Hz to 0.1Hz adjustable small increment of 0.01Hz (10 frequencies) |
Frequency Optimization | Yes |
Maximum Output Load Capability (@ maximum voltage and frequency) | 0.5µF *5000ft *1.5km |
Metering | Voltage: 0.1kV Resolution ±1% Accuracy Current: 1 µA Resolution ±1% Accuracy Capacitance: 0.1 nF to 20 µF Range Resistance: 0.1MΩ to 5GΩ Range Timing: Included and integrated Fast Arc/Flashover: Detection Included and Integrated Waveform: Real time oscilloscope display of actual output voltage waveform |
Output Mode (all load independent & symmetrical) | VLF AC Sinewave VLF AC Squarewave DC (both Positive and Negative Polarity) Fault Condition Mode / Fault Trip Mode Vacuum Bottle Test Mode (DC) - optional Cable Jacket / Sheath Test Mode |
Output Duty | Continuous |
Computer Interface | USB Flash & BT HVA Control Center Software included with every HVA instrument |
Memory / Test Record Storage | Built in Memory 50 Test Records USB Flash Drive Unlimited (see options) |
No. of programmable Automatic Test Sequences | 40 |
Standard HV Test Lead Cable Included | 13ft / 4m |
Weight | 31lbs / 14kg |
Dimensions | Imperial (inches): 16.9 x 9.4 x 13.4" Metric (mm): 430 x 240 x 340 mm |
Environmental | Storage: -13°F to 158°F / -25°C to 70°C Operating: 23°F to 113°F / -5°C to +45°C Humidity: 85% RH non-condensing |
Note:
* Based on typical MV cable. 100pf/ft or 330 pF/m
Due to continuous development, the information may change without notice.
Specifications | |
VLF/DC Hipot Tester | |
Model Overview | |
Model | Description |
With Integrated Tan Delta | |
HVA28TD | Output Voltage: 29kV, 21kVrms, Load: 0.5µF @ 0.1Hz @ 20kVrms, Weight: 31lbs/14 kg |
HVA34TD | Output Voltage: 34kV, 24kVrms Load: 1.5µF @ 0.1Hz @ 24kVrms, Weight: 44lbs/20 kg |
HVA45TD | Output Voltage: 45kV, 32.3kVrms Load: 1.0µF @ 0.1Hz @ 32kVrms, Weight: 86lbs/39 kg |
VLF/DC Only - HVA Series | |
HVA34 | Output Voltage: 34kV, 24kVrms Load: 0.5µF @ 0.1Hz @ 24kVrms, Weight: 44lbs/20 kg |
HVA30-7 | Output Voltage: 34kV, 24kVrms Load: 6.0µF @ 0.1Hz @ 24kVrms, Weight: 125lbs/57 kg |
HVA60 | Output Voltage: 62kV, 44kVrms Load: 1.0µF @ 0.1Hz @ 44kVrms, Weight: 126lbs/57 kg |
HVA90 | Output Voltage: 90kV, 64kVrms Load: 1.0µF @ 0.1Hz @ 64kVrms, Weight: 280lbs/127 kg |
HVA120 | Output Voltage: 120kV, 85kVrms Load: 0.5µF @ 0.1Hz @ 85kVrms, Weight: 436lbs/198 kg |
HVA200 | Output Voltage: 200kV, 141kVrms Load: 0.6µF @ 0.1Hz @ 141kVrms, Weight: 2,094lbs/950 kg |