The L-69-80D LOAD BANK is designed to provide a temporary load for field servicing and testing 480VAC and 208VAC three phase, 60HZ generators and inverters. The L-69-80 load bank is air cooled. A 120VAC outlet is required to operate the fans and relays. The load is 100KW at 480VAC and 80KW at 208VAC. This unit will also test 120VAC & 240VAC single phase.
| Key Features |
| Load steps: 12.5, 12.5, 25, 25, 25 KW on three phase 480VAC |
| Load steps: 5 or 10, 10, 20, 20, 20 KW on three phase 208VAC |
| Load steps: 6.5, 6.5, 13, 13, 13 KW on single phase 240VAC |
| Load steps: 1.6, 1.6, 3.2, 3.2, 3.2 KW on single phase 120VAC |
| Tests 240VAC three phase, 240VAC single phase and 120VAC single phase |
| Plug test pins for connecting test leads |
| Cam-Lok connectors |
| Meters: Digital Multimeter |
| Power indicator lights |
| Thermal protection |
| Carrying case |
| Specifications | |
| Load Banks | |
| Model | Description |
| DC Load Banks from 12 - 270 volts 12 to 270 Volts | |
| L-10T | Load Bank Multiple Loads @ 12, 24, 36, and 48VDC |
| L-24-350 | Load Bank 0-350 Amps @ 24VDC |
| L-28-350 | Load Bank 0-350 Amps @ 28VDC |
| L-28 | Load Bank 1600 Amps @ 28VDC |
| L-29 | Load Bank 2000 Amps @ 28VDC |
| L-42-350 | Load Bank 0-350 Amps 24, 36, and 48VDC |
| L-42-500 | Load Bank 0-500 Amps @ 24, 36, and 48VDC |
| L-48-350 | Load Bank 0-350 Amps @ 48VDC |
| L-48-500 | Load Bank 0-500 Amps @ 48VDC |
| L-641 | Load Bank 12-120 VDC |
| L-121-250 | Load Bank 250 AMPS @ 120 VDC |
| L-270-45 | Load Bank 45KW @ 270VDC |
| L-270 | Load Bank 72KW @ 270 VDC |
| L-121-500 | Load Bank 500 AMPS @ 120 VDC |
| AC Load Banks from 120-480 volts | |
| L-63 | Load Bank 30KW @ 208 3 Phase 60HZ |
| L-6100 | Load Bank 100KW @ 208 3 PHASE |
| L-69-80D | Load Bank 100KW @ 480VAC 80KW @ 208VAC |
| L-67 | Load Bank 70KW @ 208 3 Phase 60HZ |
| L-69-57 | Load Bank 1KW steps @ 480/208 Volts AC |
| L-6100D | Load Bank 100 KW @208 3 Phase |
| 400HZ Load Banks from 40-120KW | |
| L-40 | Load Bank 40KW @ 400HZ |
| L-72 | Load Bank 72KW @ 400HZ |
| L-80 | Load Bank 80KW @ 400HZ |
| L-100D | Load Bank 100KW @ 400HZ |
| L-120 | Load Bank 120KW @ 400HZ |